Actionneur de protection solaire (DC-rail din)
  • Actionneur de protection solaire (DC-rail din)

KNX sun shading actuators (DC - REG)

Programming tip:

When programming Warema actuators it is important to check the parameter "behaviour in case of bus voltage failure" is set on "deactivate alarm". If not when bus voltage comes back, after failure, the actuator will be blocked. Even if no security has been set.

 All the security objects have to be checked.